Ampacity chart — copper and aluminum, NEC Table 310.16
Allowable ampacity in amperes for insulated conductors rated up to 2,000 V, not more than three current-carrying conductors in a raceway, cable or earth, based on a 30°C ambient. Aluminum has no NEC-rated size below 12 AWG, so those cells are genuinely empty rather than omitted.
NEC Table 310.16 allowable ampacity by wire gauge, conductor material and temperature rating | Copper | Aluminum |
|---|
| AWG | 60°C | 75°C | 90°C | 60°C | 75°C | 90°C |
|---|
| 14 | 15 | 20 | 25 | — | — | — |
|---|
| 12 | 20 | 25 | 30 | 15 | 20 | 25 |
|---|
| 10 | 30 | 35 | 40 | 25 | 30 | 35 |
|---|
| 8 | 40 | 50 | 55 | 35 | 40 | 45 |
|---|
| 6 | 55 | 65 | 75 | 40 | 50 | 55 |
|---|
| 4 | 70 | 85 | 95 | 55 | 65 | 75 |
|---|
| 3 | 85 | 100 | 115 | 65 | 75 | 85 |
|---|
| 2 | 95 | 115 | 130 | 75 | 90 | 100 |
|---|
| 1 | 110 | 130 | 145 | 85 | 100 | 115 |
|---|
| 1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
|---|
| 2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
|---|
| 3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
|---|
| 4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
|---|
To size a conductor for a specific load and run length rather than reading it off a table, use the wire gauge calculator, which checks ampacity and voltage drop together.
The 90°C column is a trap, and it is there on purpose
THHN is a 90°C insulation. Reading across to the 90°C column for 12 AWG copper gives 30 amps, and it is tempting to conclude that a #12 THHN conductor is good for 30 A. It is not, and the reason is NEC 110.14(C): a conductor must be sized at the temperature rating of the lowest-rated termination anywhere in the circuit.
Breakers, lugs and device terminals are typically listed for 60°C or 75°C. The wire may tolerate 90°C, but the screw it lands on does not, and heat travels. So for most circuits the 75°C column is your ceiling, and for a good deal of residential equipment it is the 60°C column. The 90°C rating is not decoration — it is the starting value for derating arithmetic, where you begin at 90°C, apply the adjustment and correction factors, and then confirm the result still clears the termination limit. You never simply install to it.
14, 12 and 10 AWG have a separate ceiling
The three smallest common gauges are governed by NEC 240.4(D) as well as by the table. Whatever column your insulation qualifies for, overcurrent protection is capped at the 60°C value:
| Copper | 60°C | 75°C | 90°C | Max breaker |
|---|
| 14 AWG | 15 | 20 | 25 | 15 A |
|---|
| 12 AWG | 20 | 25 | 30 | 20 A |
|---|
| 10 AWG | 30 | 35 | 40 | 30 A |
|---|
This is why a 12 AWG branch circuit is a 20 amp circuit in every house in America even though the wire is rated 30 A at 90°C. The rule exists because small conductors have little thermal mass and terminate in devices that were never tested at those temperatures. There are narrow exceptions in 240.4(E) and (G) for specific applications, but for general branch circuits the cap is the cap.
Aluminum does not track copper by a fixed offset
The rule of thumb is "go up two sizes for aluminum." It is close enough to be useful and wrong often enough to be worth checking. At 75°C:
| Gauge | Copper | Aluminum | Al to match Cu |
|---|
| 6 AWG | 65 A | 50 A | 4 |
|---|
| 4 AWG | 85 A | 65 A | 2 |
|---|
| 2 AWG | 115 A | 90 A | 1/0 |
|---|
| 1/0 AWG | 150 A | 120 A | 3/0 |
|---|
| 4/0 AWG | 230 A | 180 A | > 4/0 |
|---|
Aluminum is still the right choice for many service and feeder runs — it costs less and weighs less, and the larger conductor is not usually a problem in a straight run. It becomes a problem in a conduit sized before anyone decided which metal was going in it, because the bigger conductor changes the conduit fill calculation too.
The two derates that shrink the table
The chart's assumptions are stated in its own title, and both fail in ordinary work. More than three current-carrying conductors in a raceway triggers the adjustment factors of NEC 310.15(C)(1), which reduce ampacity in steps as the count rises. Neutrals sometimes count and sometimes do not; equipment grounding conductors never do.
Ambient temperature above 30°C triggers the correction factors of 310.15(B). An unconditioned attic in a hot climate is comfortably outside the table's basis, and rooftop conduit in sun is further outside it again. The two factors multiply — a full conduit in a hot attic can land a conductor well below what the chart suggests, and that combination is where undersized runs usually come from rather than from misreading a single number.
What this chart cannot tell you
Ampacity answers one question: will this conductor overheat carrying this current. It says nothing about whether the voltage arriving at the far end is still usable. On a short run that does not matter. On a long one it decides the answer, and it is entirely possible for a conductor that passes ampacity comfortably to fail voltage drop badly.
That check needs conductor resistance and run length rather than a table lookup — the voltage drop formula walks through it by hand. For a specific load, run length and amperage, the wire size by amperage guide gives the direct answer for the common circuit sizes.