Skip to content
Measure the Build logoMeasure the Build

Electrical

Wire Gauge Calculator

Find the minimum AWG wire size for a circuit from load current, one-way run length, and voltage — checked against both NEC Table 310.16 ampacity and the NEC 210.19(A) voltage-drop recommendation. Also called a wire size calculator or voltage drop calculator; same tool either way. Works for copper or aluminum, household AC or 12V/24V DC.

What do you want?
A

The breaker/fuse rating, or the actual continuous draw.

ft

Source to load, one direction — not the round trip.

V

120/240 for household circuits; 12/24/48 for solar, RV, or marine DC.

Conductor material

NEC does not rate aluminum below 12 AWG — sizing skips straight to the next size up when that matters.

Insulation temperature rating

Standard NM-B (Romex) sheathed cable is 90°C rated wire, but NEC 334.80 requires sizing it off the 60°C ampacity column for ordinary residential installation. Pick 60°C unless you know your installation qualifies for a higher column.

Minimum wire size

10 AWG

35 A ampacity · 2.02% voltage drop

2.42 V dropped over 50 ft one-way

Voltage drop, not ampacity, set the minimum size for this run.

The working
Load20 A at 120 V, one-way run 50 ft
Ampacity needed (75°C column)copper 10 AWG rated 35 A ≥ 20 A
Resistancecopper 10 AWG = 1.21 Ω/1000 ft
Voltage drop2 × 1.21 × 20 × 50 ÷ 1000 = 2.42 V
Percent of source voltage2.42 ÷ 120 × 100 = 2.02%
Target≤ 3% recommended (NEC 210.19(A))

Planning estimate only. Check the result against current product instructions, local requirements, and your own takeoff. See the calculator disclaimer.

Ampacity is not the whole story

Most "what gauge do I need" answers stop at ampacity — look up the amps, read off a wire size, done. That is correct for a short run and incomplete for a long one. A 20A circuit only needs 12 AWG copper to stay under its 25A rating, but 12 AWG run 50 ft one-way at 120V loses 3.2% of the source voltage — over the 3% NEC 210.19(A) recommendation for a branch circuit alone. The honest minimum for that run is 10 AWG, one size up from what ampacity alone would suggest. Length, not just load, decides the wire.

Romex, THHN, and the column that trips people up

NEC Table 310.16 has three ampacity columns — 60°C, 75°C, and 90°C — and which one applies depends on insulation, not just wire size. Standard NM-B sheathed cable (Romex) uses conductors rated 90°C, but NEC 334.80 requires ordinary residential installation to be sized off the 60°C column regardless. That 90°C rating matters for other derating math, not for picking your ampacity here. THWN pulled through conduit is the usual 75°C case; THHN in a dry attic or crawlspace can use 90°C. Guessing the wrong column is the easiest way to under-size a Romex run.

Copper vs. aluminum

Aluminum costs less per foot but needs roughly two AWG sizes more than copper for the same ampacity — 10 AWG copper (35A at 75°C) only gets you to 8 AWG aluminum territory (40A), and NEC does not rate aluminum below 12 AWG at all. Aluminum branch-circuit wiring installed before the mid-1970s has a documented history of connection failures at devices never rated for it; modern practice reserves aluminum mostly for larger feeders and service conductors with connectors rated "CO/ALR" or "AL/CU." If you are working on existing aluminum branch wiring rather than sizing new feeder, stop and call a licensed electrician.

AWG wire size chart — ampacity and resistance at 75°C

The 75°C column, the rating most THWN-in-conduit and general-purpose work uses. Resistance is DC resistance at 75°C from NEC Chapter 9, Table 8 — what the calculator's voltage-drop math runs on regardless of which ampacity column you pick above.

AWGCu ampacityAl ampacityCu Ω/1000ftAl Ω/1000ft
1420 A3.07
1225 A20 A1.933.18
1035 A30 A1.212
850 A40 A0.7641.26
665 A50 A0.4910.808
485 A65 A0.3080.508
3100 A75 A0.2450.403
2115 A90 A0.1940.319
1130 A100 A0.1540.253
1/0150 A120 A0.1220.201
2/0175 A135 A0.09670.159
3/0200 A155 A0.07660.126
4/0230 A180 A0.06080.1

Full 60/75/90°C columns for both materials, 14 AWG through 4/0, are in the calculator above and cited below.

What this tool does not do

No derating for more than three current-carrying conductors bundled in one raceway or cable (NEC Table 310.15(C)(1)), no check against a breaker or device's terminal temperature rating even when it is lower than the wire's own rating, and no sizing above 4/0 AWG. The voltage-drop percentages are NEC Informational Notes — recommended, not a national requirement — though a number of states and cities (California and New York City among them) enforce them locally. This tool estimates a single ordinary circuit; it is not a substitute for a licensed electrician on a subpanel, service entrance, or any run with bundled conductors.

For the underlying tables and the rules this tool applies, three guides go deeper than the calculator can: the NEC ampacity chart covers why the 90°C column is rarely the one you may use, wire size by amperage gives the direct answer for 20 through 200 amp circuits including the 83% dwelling service allowance, and the voltage drop formula works the arithmetic by hand.

Sources

Grouped by manufacturer or publisher, then by document. Expand a group for the cited document, its verified-on date, and every value taken from it — all of it stays in the HTML either way.

NFPA(14 documents, 102 values)

Frequently asked questions

What size wire do I need for a 20 amp circuit?

12 AWG copper is the NEC ampacity minimum for a 20A branch circuit (25A rated at the 75°C column, comfortably above the 20A load). But ampacity is not the only check — run that same circuit 50 ft one-way at 120V and 12 AWG hits 3.2% voltage drop, over the 3% NEC 210.19(A) recommendation. The honest minimum for that length is 10 AWG. Enter your own amps and length above rather than trusting a flat "20A = 12 AWG" rule.

What is the difference between a wire gauge calculator and a voltage drop calculator?

They are two views of the same math. A wire gauge (or wire size) calculator answers "what AWG do I need"; a voltage drop calculator answers "how much voltage do I lose over this run." Both need the same inputs — amps, one-way length, voltage, material — and this tool runs both directions: pick "Find the minimum wire size" for the first question, "Check a wire size I already have" for the second.

What wire size do I need for 12 volt DC — solar, RV, or marine?

Bigger than most people expect, because the 3% voltage-drop target is 3% of a much smaller number. At 120V, 3% is 3.6V of headroom; at 12V, 3% is only 0.36V. The same 20A load over the same 50 ft run that needs 10 AWG copper at 120V needs 1 AWG copper at 12V to stay under 3% drop — three sizes bigger for the same current, purely because the base voltage is smaller. Set the voltage field to 12 (or 24/48) and the calculator runs the identical formula — it does not need a separate "12 volt wire size calculator."

Does this account for Romex (NM-B) derating?

Partly, and the temperature-rating selector is why. Standard NM-B sheathed cable (Romex) is manufactured with 90°C-rated conductors, but NEC 334.80 requires ordinary residential installations to be sized off the 60°C ampacity column, not the 90°C column the insulation is rated for — the 90°C rating mainly matters for derating math with bundled conductors, not straight ampacity. Pick "60°C — NM-B/Romex" unless you specifically know your installation qualifies for a higher column.

What size aluminum wire do I need compared to copper?

Roughly two AWG sizes bigger for the same ampacity — 10 AWG copper (35A at 75°C) needs 8 AWG aluminum to only reach 40A, so in practice aluminum branch circuits typically jump to the next size up from the copper equivalent. NEC also does not rate aluminum below 12 AWG at all. Aluminum branch-circuit wiring has a documented history of connection-related failures at older devices not rated for it (look for "CO/ALR" on the switch or outlet); if you are touching existing aluminum branch wiring rather than sizing a new feeder, that is a job for a licensed electrician, not a calculator.

Does this include derating for bundled conductors or terminal ratings?

No, on purpose rather than by mistake. NEC Table 310.15(C)(1) reduces ampacity further when more than three current-carrying conductors share a raceway or cable, and a breaker or device with a lower terminal temperature rating than the wire caps what column you can actually use. Both require details about the specific installation this tool does not collect. Treat this calculator as a starting point for ordinary single-circuit runs, and get a licensed electrician to size anything with bundled conductors, a subpanel feeder, or a service entrance.