Skip to content
Measure the Build logoMeasure the Build

Electrical

Box Fill Calculator

Work out whether what you are putting in the box actually fits, under NEC 314.16. Every allowance is itemised by the paragraph it comes from — (B)(1) through (B)(5) — so the result can be checked line by line rather than taken on trust.

If the box is stamped with its volume, use that instead of the table — a box with a plaster ring or extension is the sum of the marked volumes, and it is usually larger than the table figure.

Conductors entering the box

Count each conductor that comes in and is spliced or terminated. Do not count grounds here — they go in their own field below.

A yoke is the strap a switch or receptacle mounts on, and each one costs a double allowance — usually the largest single item in the box. Fixture studs and hickeys go in support fittings.

One allowance total, however many clamps are inside. Connectors that clamp outside the box do not count at all.

Required

16.00

cubic inches

Box holds 12.5 in³

Over — box too small

The working

(B)(1) conductors: 8.00 in³

(B)(2) clamps: 2.00 in³

(B)(3) support fittings: 0.00 in³

(B)(4) device yokes: 4.00 in³

(B)(5) grounds: 2.00 in³

Total required = 16.00 in³

Box volume = 12.5 in³

Remaining = -3.50 in³

Planning estimate only. Check the result against current product instructions, local requirements, and your own takeoff. See the calculator disclaimer.

Five paragraphs, added up

Box fill has a reputation for being fiddly, and it is really just five rules that get added together. Conductors count once each at their own size. Internal clamps count once in total, no matter how many there are. Each support fitting — a fixture stud or hickey — counts once. Each device yoke counts twice. All the grounds together count once. Then you compare that total against what the box actually holds.

The detail that trips people is which conductor size each rule uses. Only the first rule uses each conductor's own size. Clamps, fittings, yokes and grounds are all taken at the largest conductor in the box. So running a single 12 AWG into a box otherwise full of 14 AWG does not add 2.25 cubic inches — it also raises the clamp allowance and every yoke allowance to the 12 AWG figure. One wire can push a box over on its own.

The device yoke is the expensive one

A switch or receptacle takes a double allowance under 314.16(B)(4). At 12 AWG that is 4.5 cubic inches for the yoke alone, before a single conductor is counted — more than any other single item in a typical box. Anyone estimating fill in their head almost always counts the wires and forgets that the device itself is the largest consumer.

This is why the classic failure is so ordinary. Two 14/2 cables into a 3 × 2 × 2½ device box with one switch: eight cubic inches of conductor, two for the clamps, four for the yoke, two for the grounds. Sixteen cubic inches into a box that holds twelve and a half. That combination is in millions of houses, and it is the default loaded above precisely because it fails — a calculator that opens on a passing example teaches you nothing.

Grounds, and a 2020 change

Grounds have always been generous: however many equipment grounding conductors arrive, they shared a single volume allowance based on the largest one. The 2020 NEC narrowed that. The single allowance now covers up to four grounds, and each conductor beyond four adds a quarter allowance.

For nearly every residential box this changes nothing, because four grounds is already a busy box. It matters in a multi-gang box fed by several circuits, and it matters that the two editions genuinely disagree — so this calculator applies the 2020 rule and warns you on screen once you go past four, rather than silently picking an edition. Confirm which cycle your jurisdiction has adopted before leaning on a marginal result.

Use the marked volume when there is one

Table 314.16(A) lists the standard boxes, and this calculator carries all twenty of them. But the table is a fallback. A box marked with its own volume uses that figure, and where a plaster ring or extension ring is fitted, the assembly is the sum of the marked volumes. Those additions are frequently the difference between failing and passing, and they are stamped on the parts — worth reading before deciding a box has to come out.

Related checks that are separate calculations: how many conductors fit in the raceway feeding the box is a conduit fill question under NEC Chapter 9, and what size those conductors need to be is a wire gauge question under 310.16 and voltage drop. Box fill only asks whether what you have chosen will physically and legally fit in the enclosure.

Sources

Grouped by manufacturer or publisher, then by document. Expand a group for the cited document, its verified-on date, and every value taken from it — all of it stays in the HTML either way.

NFPA(8 documents, 32 values)

Frequently asked questions

How do I calculate box fill?

Add five things from NEC 314.16(B) and compare the total against the box volume. One allowance per conductor at its own size; one allowance total if any internal clamps are present; one per support fitting; a double allowance per device yoke; and one for all the grounds together. Every allowance except the conductors themselves is taken at the largest conductor in the box.

How many cubic inches does a 12 AWG wire need?

2.25 cubic inches, from NEC Table 314.16(B). For comparison 14 AWG needs 2.00, 10 AWG needs 2.50, 8 AWG needs 3.00 and 6 AWG needs 5.00. Note the jump at 6 AWG — it is nearly double 8 AWG, which catches people adding a feeder to an existing box.

Why does a switch or receptacle count as two conductors?

NEC 314.16(B)(4) requires a double volume allowance for each yoke or strap, based on the largest conductor connected to it. A single 12 AWG switch therefore consumes 4.5 cubic inches before you count a single wire. It is usually the biggest item in the box and the one most often left out of a mental estimate.

Do ground wires count in box fill?

Yes, but collectively rather than individually. All the equipment grounding conductors together take a single volume allowance based on the largest one present. The 2020 NEC changed this: the single allowance now covers up to four grounds, and each one beyond four adds a quarter allowance. Under earlier editions any number of grounds counted as one, so which applies depends on the code cycle your jurisdiction has adopted.

Will two 14/2 cables and a switch fit in a 3x2x2.5 device box?

No. Four 14 AWG conductors are 8 cubic inches, the internal clamps add 2, the switch yoke adds 4, and the two grounds add 2 — 16 cubic inches against a box that holds 12.5. That exact combination is extremely common in older houses and is the default shown above, because it fails. A 4 × 2⅛ square box at 30.3 cubic inches takes the same load with room to spare.

Can I use the volume marked on the box instead of the table?

Yes, and you usually should. Table 314.16(A) covers standard boxes, but a box marked with its own volume by the manufacturer uses that figure, and an assembly of box plus plaster ring or extension ring is the sum of the marked volumes. That total is often noticeably larger than the table value, which can be the difference between passing and re-boxing.