Skip to content
Measure the Build logoMeasure the Build

Roofing

Soffit Calculator

How many panels cover the eave — and, the part nobody else answers, whether that soffit actually delivers the net free area the code asks for.

ft
in

Eave run is the total length of soffit, both sides added together. Overhang is the depth from the wall to the fascia — measure it, do not assume 24 in.

sq ft

The vented space below the roof, not the house footprint — they differ wherever the attic does not run over the whole plan. This drives the ventilation requirement only; leave it at 0 if you just want the panel count.

IRC R806.2 requires 1/150. The 1/300 exception halves it, but only if BOTH conditions are met: a Class I or II vapour retarder in Climate Zones 6–8, and 40–50% of the vent area up near the ridge. It is not a free choice.

Published net free area, not the size of the hole. Lanced aluminium is quoted as a 4–7 range and the low end is used here, which is why it can be under a third as open as perforated over identical soffit.

Panels run 12 ft. Coverage is the nominal width times that length, so a 12 in panel covers 12 sq ft.

%

Applied to the panel area only. Soffit waste is driven by how your overhang divides into a 12 ft panel, plus corners and returns — not by breakage.

Order

22

panels

240 sq ft soffit · intake meets code

The working

Soffit: 120 ft × 24 in ÷ 12 = 240 sq ft

+ 10% = 264 sq ft

Panels: 264 ÷ 12 sq ft = 22 → 22

NFA required: 1500 ÷ 150 × 144 = 1,440 sq in

Split 50/50: intake 720 sq in · exhaust 720 sq in

Intake available: 14 × 240 sq ft = 3,360 sq in

Ridge to balance: 720 ÷ 18 = 40 ft

Planning estimate only. Check the result against current product instructions, local requirements, and your own takeoff. See the calculator disclaimer.

Vented soffit and ventilating soffit are not the same thing

Two aluminium soffit panels can look identical from the ground and differ by a factor of three in how much air they pass. Air Vent publishes perforated aluminium soffit at 14 square inches of net free area per square foot, and lanced aluminium at 4 to 7. Perforated panels are punched with round holes; lanced panels are slit and pushed open, and the slits close up far more than they appear to.

This calculator uses the low end of that published range, 4, for the same reason the thinset pages on this site count from the low end of a coverage range: the conservative figure is the one that does not leave you short. But the honest answer is that a 4-to-7 range is nearly two to one, so if you are relying on lanced soffit to carry your intake, find the number for the panel you are actually buying.

It is the most common reason an attic with apparently continuous vented soffit still runs hot. The second most common is imbalance, which the page also flags — see below.

1/150 is the rule; 1/300 is a conditional exception

Most ventilation advice leads with the 1/300 ratio, which has it backwards. IRC R806.2 states plainly that "the minimum net free ventilating area shall be 1/150 of the area of the vented space." The 1/300 figure is an exception with two conditions attached, and both must be met: a Class I or II vapour retarder on the warm-in-winter side of the ceiling in Climate Zones 6, 7 and 8, and between 40 and 50 percent of the required vent area located in the upper portion of the attic, within 3 feet of the ridge.

Note the second condition is a band with a ceiling, not just a floor. You cannot qualify by putting 60 percent of your vent area at the ridge — more exhaust is not better here. That is the code's way of saying the same thing the manufacturers say about balance, and it is why an even intake/exhaust split is the most exhaust the exception allows.

The other place this arithmetic goes wrong is units. The code states a ratio of areas in square feet; every vent product on the market is published in square inches. The factor of 144 between them is a step this calculator does in one place and shows in the working, because dropping it is an error of two orders of magnitude that still produces a plausible-looking number.

What we found auditing the manufacturer's own tables

Air Vent's Principles of Attic Ventilation carries two appendix tables: attic area against minimum ridge length, and ridge length against the intake needed to balance it. Both are reproduced widely. We recomputed every cell.

Appendix A reconciles exactly — every row is the attic area divided by the ratio, converted to square inches, halved for the intake/exhaust split, and divided by the 18 square inches per foot their ridge vents deliver — with one exception. The row printed as 2,600 square feet does not reconcile at either ratio. The value that does, exactly, is 2,700, which also restores the even 300 square foot step the rest of the table follows. It is a typo, and our test asserts both halves of that finding so the claim cannot rot.

Appendix B is more interesting. Its vent counts are rounded to nearest, not rounded up — we checked all 27 cells, and round-to-nearest matches every one while rounding up differs on ten. The consequence is that ten of those 27 published combinations give you slightly less intake net free area than the ridge is exhausting, up to 6.7 percent short in the worst case. That quietly contradicts the booklet's own rule a few pages earlier, that intake "should be equal to or greater than" exhaust. This calculator rounds vent counts up, always, and a test asserts our counts never land below the published figures.

The 7/16 rule hiding in the vent table

Air Vent lists three undereave vents: 16×8 inch at 56 square inches of net free area, 16×6 at 42, and 16×4 at 28. Divide each by its gross opening and you get 0.4375 every time — exactly 7/16. The whole published range sits on one line, so the louvres and screen cost a consistent nine sixteenths of the hole.

That is a property of these particular published figures rather than a law of vents, and a different manufacturer's louvre will have a different ratio. But it is a useful sanity check on any vent you are quoted: if someone claims net free area much above 45 percent of the gross opening for a screened louvre, ask how it was measured. The relationship is exact enough that a test pins it, the same way this site pins Quikrete's 0.0075 cubic feet per pound.

One more relationship worth knowing when you are balancing a system: continuous ridge vent runs 18 square inches per linear foot and continuous soffit strip runs 9 — exactly half. So a balanced install needs two feet of soffit strip for every foot of ridge, which is where Air Vent's own balancing table comes from. Once the soffit is sized, the roofing shingles calculator handles the field above it, and the attic insulation calculator covers the floor below — just keep the insulation out of the soffit path, because a blocked vent has a net free area of zero no matter what the panel is rated at.

Sources

Grouped by manufacturer or publisher, then by document. Expand a group for the cited document, its verified-on date, and every value taken from it — all of it stays in the HTML either way.

CertainTeed(1 document, 1 value)
ICC(1 document, 1 value)
IRC(4 documents, 4 values)
Trade conventions(2 documents, 2 values)
Other sources(12 documents, 12 values)

Frequently asked questions

How much vented soffit do I need?

Work it in two steps. IRC R806.2 asks for net free ventilating area of 1/150 of the attic floor, and about half of that should be intake at the soffit. So a 1,500 sq ft attic needs 10 sq ft of total NFA — 1,440 square inches — of which roughly 720 square inches is intake. Then divide by what your product actually delivers. Perforated aluminium soffit is about 14 square inches per square foot, so you need around 51 sq ft of it. The trap is that a soffit can look fully vented and deliver a fraction of that.

How many soffit panels do I need?

Soffit area is the total eave run times the overhang depth. A house with 120 linear feet of eave and a 24 inch overhang has 240 square feet of soffit. Panels come 12 feet long in 12 inch (usually vinyl) or 16 inch (usually aluminium) widths, so a 12 inch panel covers 12 square feet and you would need 20 before waste, 22 with 10% overage. Waste on soffit is mostly about how your overhang divides into a 12 foot panel, plus corners and returns.

Is attic ventilation 1/150 or 1/300?

1/150 is the rule and 1/300 is the exception, which is the opposite of how most sources present it. IRC R806.2 permits 1/300 only when both conditions are met: in Climate Zones 6, 7 and 8 a Class I or II vapour retarder on the warm-in-winter side of the ceiling, and 40 to 50 percent of the required vent area up in the upper portion of the attic, within 3 feet of the ridge. Miss either and you are back on 1/150. Halving your ventilation because a calculator offered you the option is not a decision to take casually.

What is net free area on a soffit vent?

The actual unobstructed opening air can pass through, after the louvres and insect screen take their share — always well under the size of the hole. It is worth seeing how much is lost: Air Vent publishes 56 square inches for a 16×8 inch undereave vent, but 16 × 8 is 128 square inches of gross opening. That is 43.75 percent, and the same 7/16 ratio holds exactly across their 16×6 and 16×4 vents too. So a bit over half the opening is doing nothing but keeping wasps out.

Why is my attic hot if I have vented soffit?

The likeliest reason is that your soffit is lanced rather than perforated. Air Vent publishes lanced aluminium soffit at 4 to 7 square inches per square foot, against 14 for perforated — so identical-looking soffit can deliver under a third of the airflow. The second likeliest is that intake is short of exhaust. If the ridge vent can pull more air than the soffits can supply, it makes up the difference by pulling air back down through itself, and the far end of the attic never moves. Both show up on this page, because it compares what your soffit delivers against what the ridge needs.

Should intake and exhaust ventilation be equal?

Equal at minimum, and if anything favour intake. Air Vent puts it plainly: intake net free area "should be equal to or greater than the net free area of exhaust vents". The code agrees from the other direction — R806.2 caps upper-portion area at 50 percent of the total, so an even split is the most exhaust the exception permits and any imbalance has to fall on the intake side. Continuous ridge vent runs about 18 square inches per foot and continuous soffit strip about 9, exactly half, which is why a balanced system needs two feet of soffit strip for every foot of ridge.